240mm2 300mm2 Single Core XLPE Power Cable

Product Details
Customization: Available
Application: Construction, Underground, Power Station, Telecommunication
Voltage: Middle Voltage Cable
Still deciding? Get samples of US$ 50/Meter
Order Sample
Shipping & Policy
Shipping Cost: Contact the supplier about freight and estimated delivery time.
Payment Methods:
visa mastercard discover JCB diners club american express T/T
PIX SPEI OXXO PSE OZOW
  Support payments in USD
Secure payments: Every payment you make on Made-in-China.com is protected by the platform.
Refund policy: Claim a refund if your order doesn't ship, is missing, or arrives with product issues.
Manufacturer/Factory & Trading Company

360° Virtual Tour

Secured Trading Service
Diamond Member Since 2023

Suppliers with verified business licenses

Audited Supplier

Audited by an independent third-party inspection agency

Number of Employees
285
Year of Establishment
2007-11-13
  • 240mm2 300mm2 Single Core XLPE Power Cable
  • 240mm2 300mm2 Single Core XLPE Power Cable
  • 240mm2 300mm2 Single Core XLPE Power Cable
  • 240mm2 300mm2 Single Core XLPE Power Cable
  • 240mm2 300mm2 Single Core XLPE Power Cable
  • 240mm2 300mm2 Single Core XLPE Power Cable
Find Similar Products

Basic Info.

Model NO.
YJV
Insulation Material
XLPE
Sheath Material
PVC/XLPE
Material Shape
Round Wire
Wire Core Material
Bare Copper Wire
Certification
ISO, CCC, CE, RoHS, VDE
Model
YJV
Brand
Qinshan
Name
PVC/XLPE Power Cable
Market
Global
Hot Sale Size
70mm, 120mm,400mm,95mm
Other Core
1 Core, 3 Core
Type
Middle Voltage
Middle Voltage
8.7/15kv
Transport Package
Wooden Drum
Specification
1x25~1000mm2; 3x25~400mm2
Trademark
QINSHAN
Origin
China
HS Code
8544492100
Production Capacity
8000000meters/Month

Packaging & Delivery

Package Size
10.00cm * 10.00cm * 5.00cm
Package Gross Weight
0.500kg

Product Description

240MM2 300MM2 Single Core XLPE Power Cable


Introduction:

        For XLPE insulated power cable, either chemical method or physical method is employed to transform the molecular structure of PE from chain into three-dimensional network, i.e. thermo-plastic PE is transformed into thermosetting XLPE. After cr·oss-linking, the thermal and mechanical properties of PE have been greatly improved while its excellent electrical property are still retained.

       The maximum permissible operating of the conductor of a XLPE insulated power cable is 90°C.which is higher than that of paper, PVC or PE insulated power cable. The cable has the advantage of simplicity in construction, lightness in weight, convenience in application besides its excellent electrical, thermal, mechanical and anti-chemical corrosion properties. It can also be laid with no limitation of level difference along the route.

       The mechanical and electrical properties of these cables are accordant with GB/T12706-2002 Power cables extruded insulation and their accessories of elated voltages 1kV(Um=1.2kV)up to 35kV(Um=40.5kV) and IEC60502-1997 Extruded insulation power cables and appendices for rated voltages 1kV up to 30kV.


Description:

1) Rated Voltage:  8.7/15KV 
2) Max. working temperature: 90 °c
3) Max. temperature during short circuit (≤5S): 250 °c
4) Conductor: class 1, 2 copper or aluminum
5) Sectional area: 1x25 - 1000mm2,3x25 - 400mm2
6) Insulation: XLPE
7) No. of cores: 1, 3
8) Armor: steel wire or steel tape for 3 core cables and non-magnetic material for single core
9) Oversheath: PVC/XLPE
10) Min. beding radius: 15 times cable radius for single-core cables and 12 times for multi-core ones
11) Max. conductor DC resistance at 20°c:


Stardand:

IEC 60502, 60228, 60332, 60331
DIN VDE 0276-620
HD 620 S1: 1996
DIN EN 60228 class 2 (construction)


Application:
 
Type Conductor Application
YJV/YJLV CU/AL For laying in door,tunnel,channel and underground.Unable to bear external mechanical force,but bear the traction force during laid.
YJV22/YJLV22 CU/AL For laying in tunels in door,tunnel,channel and underground.Able to bear external mechanical force,but unable to bear large pulling force.
YJV32/YJLV32 CU/AL For laying in shaft with large difference of level.Able to bear external mechanical force,and moderable pulling force.

Technical Parameters:
Nominal cross sectional area of conductor(mm²) lnsulation thickness (mm) Sheath thickness (mm) Approx. overall diameter of cable(mm) Approx.weight Of cable (kg/km) D.C resistance of conductor(Ω/km) Testing voltage     A.C Current rating
In air(A) Direct in soil(A)
Cu AI Cul Al (kV/5min) Cu Al Cu Al
1x25 4.5 1.8 23 680 525 ≤0.727 ≤1.20 30.5 140 110 150 115
1x35 4.5 1.8 24 804 587 ≤0.524 ≤0.868 30.5 175 135 180 135
1x 50 4 5 1.9 25 984 674 ≤0.387 ≤0.641 30.5 205 160 215 160
1 x70 4 5 1.9 27 1201 768 ≤0.268 ≤0.443 30.5 260 200 265 200
1x 95 4 5 2.0 29 1490 902 ≤0.193 ≤0.320 30.5 315 245 315 240
1x 120 4.5 2.0 30 1765 1022 ≤0.153 ≤0.253 30.5 365 285 360 270
1x150 4 5 2.1 32 2091 1162 ≤0.124 ≤0.206 30.5 415 320 405 305
1x 185 4 5 2.1 34 2452 1307 ≤0.0991 ≤0.164 30.5 475 370 455 345
1 x 240 4.5 2.2 36 3034 1548 ≤0.0754 ≤0.125 30.5 565 440 530 400
1 x 300 4.5 2.4 39 3672 1815 ≤0.0601 ≤0.100 30.5 645 505 595 455
1x 400 4.5 2 4 42 4646 2170 ≤0.0470 ≤0.0778 30.5 750 590 680 520
1×500 4.5 2.5 45 5651 2556 ≤0.0366 ≤0.0605 30.5 865 690 765 595
1 x630 4.5 2.5 50 7154 3248 ≤0.0283 ≤0.0469 30.5 990 800 860 680
1 x 800 4.5 2.7 55 8750 3790 ≤0.0221 ≤0.0367 30.5 1140 940 950 765
1×1000 4.5 2.9 59 10727 4527 ≤0.0176 ≤0.0291 30.5 1250 1050 1040 850
3×25 4.5 2.4 46 2573 2072 ≤0.727 ≤1.20 30.5 120 98 125 100
3 x35 4.5 2.6 48 2985 2334 ≤0.524 ≤0.868 30.5 145 115 155 120
3×50 4.5 2.7 51 3529 2598 ≤0.387 ≤0.641 30.5 175 135 180 140
3 x70 4.5 2.8 55 4197 2895 ≤0.268 ≤0.443 30.5 220 170 220 170
3 x 95 4.5 2.9 58 5230 3462 ≤0.193 ≤0.320 30.5 265 205 265 210
3x120 4.5 3.0  61 6120 3888 ≤0.153 ≤0.253 30.5 305 235 300 235
3 × 150 4.5 3.1  64 7207 4416 ≤0.124 ≤0.206 30.5 350 270 340 260
3 x 185 4.5 3.2  68 8378 4935 ≤0.0991 ≤0.164 30.5 395 310 380 300
3×240 4.5 3.4  73 10177 5712 ≤0.0754 ≤0.125 30.5 470 370 435 345
3×300 4.5 3.5  77 12159 6577 ≤0.0601 ≤0.1005 30.5 535 420 485 390
3 x 400 4.5 3.8 86 15641 8081 ≤0.0470 ≤0.0778 30.5 610 485 520 440
Product Show:
240mm2 300mm2 Single Core XLPE Power Cable

240mm2 300mm2 Single Core XLPE Power Cable
240mm2 300mm2 Single Core XLPE Power Cable240mm2 300mm2 Single Core XLPE Power Cable240mm2 300mm2 Single Core XLPE Power Cable240mm2 300mm2 Single Core XLPE Power Cable240mm2 300mm2 Single Core XLPE Power Cable240mm2 300mm2 Single Core XLPE Power Cable240mm2 300mm2 Single Core XLPE Power Cable240mm2 300mm2 Single Core XLPE Power Cable

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now
Contact Supplier
Product Groups
More